G E T T I N G S T A R T E D
6
All fire zones must be wired according to the following
diagram:
2.8.5 Fire Zone Wiring – 2-Wire Smoke Detectors
This option is for PC1575 (2-wire smoke option) only. If
PGM2 has been programmed for a 2-wire Smoke Detector
connection
,
the detectors must be wired according to the
following diagram:
2-wire smoke is only available for PC1575 with the 2-
wire smoke option because it has a 300mA PGM2.
Please refer to Appendix D “PGM Output Options” to
verify whether you have the correct output type.
If a PC1575 (2-wire smoke option) 300mA PGM2 is
programmed for 2-wire smoke support, the connec-
tor CON1 on the main board must be removed.
2.8.6 Keyswitch Zone Wiring (PGM2)
This option is available for either of either a PC1575 (standard
option) or PC1575 (2-wire smoke option). If PGM2 has been
programmed for keyswitch operation (momentary or
maintained) or 24 hour operation, the keyswitches must be
wired according to the following diagram:
2.8.7 LINKS Support
When using the LINKS 1000
cellular communicator, the
connection must be made
according to the accompanying
diagram.
2.8.8 LINKS Supervisory
When using the LINKS 1000
cellular communicator, any
zone may be configured for
LINKS Supervisory.
With a LINKS Supervisory
zone, if the LINKS 1000
experiences a trouble, the
zone will be violated, causing
the panel to report the event to
the central station. This type of
zone
always
requires a single
EOL resistor (5600Ω).
The LINKS Supervisory zone must be wired according to the
accompanying diagram.
2.8.9 LINKS Answer
When using the LINKS 1000
cellular communicator, PGM2
of either a PC1575 (standard
option) or PC1575 (2-wire
smoke option) may be
configured for LINKS Answer
(see Appendix D).(see Appendix D).
(see Appendix D).(see Appendix D).
(see Appendix D).
A PGM configured for LINKS
Answer allows downloading to
be performed in the event of
phone line failure. When the
LINKS receives a phone call, it will activate the RING
terminal on the LINKS circuit board. The PGM programmed
as LINKS Answer
always
requires a single EOL resistor
(2200Ω).
The LINKS Answer zone must be wired according to the
accompanying diagram.
The LINKS Answer zone is only required for down-
loading to the panel via the LINKS.
If PGM2 is programmed for LINKS Answer, Jumper
CON1 on the main board of a PC1575 (2-wire smoke
option) must be removed. If your PC1575 is the
standard option, then connector CON1 is already
removed (please see Appendix D “PGM Output
Options” for more information).
When using the LINKS, Busy Tone Detection must
not be used.