
G E T T I N G S T A R T E D
5
2.6 Supervision
By default, all modules are supervised upon installation.
Supervision is enabled at all times so that the panel can
indicate a trouble if a module is removed from the system.
A connected module which does not show as being present
will appear as a trouble condition and the Trouble light on the
keypad will turn ON. This condition may be due to one or more
of the following reasons:
• the module is not connected to the KEYBUS
• there is a KEYBUS wiring problem
• the module is more than 1,000'/300m from the panel
• the module does not have enough power
For more information regarding module supervision troubles,
please refer to
Section 3.4 (“[Section 3.4 (“[
Section 3.4 (“[Section 3.4 (“[
Section 3.4 (“[
✱✱
✱✱
✱
] [2] Trouble Conditions”).] [2] Trouble Conditions”).
] [2] Trouble Conditions”).] [2] Trouble Conditions”).
] [2] Trouble Conditions”).
Modules will not be automatically supervised if
connected while in installers mode.
2.7 Removing Modules
The panel must be instructed to no longer supervise a
module being removed from the system. To remove the
module, disconnect it from the KEYBUS and reset the
supervision field by entering [92] in the installer’s
programming
.
The panel will be reset to recognize and
supervise all existing modules on the system.
2.8 Zone Wiring
For a complete description of the operation of all zone types,
please refer to
Section 5.2 (“Zone Definitions”).Section 5.2 (“Zone Definitions”).
Section 5.2 (“Zone Definitions”).Section 5.2 (“Zone Definitions”).
Section 5.2 (“Zone Definitions”).
There are several different ways in which zones may be
wired, depending on which programming options have
been selected. Please refer to the following diagrams to
study each type of individually supervised zone wiring.
Any zone defined as Fire or 24 Hour Links Supervisory
will automatically require a single End of Line (EOL)
resistor regardless of which type of zone wiring
supervision is selected
.
(See Section 5.2 “Zone
Definitions”)
Reconfiguring the zone supervision from
a non-default setting—from DEOL to EOL or from NC
to DEOL—may disable zones 1-6 while open or in
trouble. To prevent this situation, the system should be
powered down completely and powered up again.
2.8.1 Normally Closed (NC) Loops
This option should only be selected if Normally Closed
(NC) detection devices or contacts are being used
.
2.8.2 Single End Of Line (EOL) Resistors (5600Ω)
This option should be selected if either Normally
Closed (NC) or Normally Open (NO) detection
devices or contacts are being used
.
2.8.3 Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if
the zone is in alarm, tampered or faulted.
This option can only be selected if Normally Closed
(NC) detection devices or contacts are being used
(ie: Do not use DEOL resistors for Fire zones or
LINKS Supervisory zones).
Only one NC contact can be connected to each
zone. Multiple detection devices or contacts on a
single loop is not allowed
.
The following chart shows zone status under certain
conditions:
• Loop Resistance ............................... Loop Status
• 0Ω (shorted wire, loop shorted) ....... Fault
• 5600Ω (contact closed).................... Secure
• Infinite (broken wire, loop open) ...... Tamper
• 11200Ω (contact open) .................... Violated
2.8.4 Fire Zone Wiring — 4-Wire Smoke Detectors
Comentarios a estos manuales