
Establishing PGM Output Types
Each PGM output is designed so that when activated by the
panel, the terminal will switch to ground.
PGM 1 – 50mA Current
PGM1 can sink up to 50 mA of current
to activate LEDs or a small buzzer.
Connect the positive side of the LED
or buzzer to AUX+, the negative side
to PGM1. If more than 50 mA of current
are required, a relay must be used.
Please study PGM wiring in the
accompanying diagram.
PGM 2 – 50mA Current (Standard Option)
Because jumper CON1 is not present on the circuit board
diagram below, the panel is a PC1575 (standard option).
This means that PGM2 is rated at 50mA and does not
support 2-wire smoke detectors.
PGM2 outputs are connected
the same way as PGM1
outputs.
PGM2 – 300mA Current (2-wire Smoke Option)
Because jumper CON1 is present on the circuit board diagram
below, the panel is a PC1575 (2-wire smoke option). This
means that PGM2 is rated at 300mA and will support 2-wire
smoke detectors. (See Section 2.8 “Zone Wiring – Fire Zone
Wiring”). Note that the jumper CON1 must be removed when
PGM2 is programmed for for Downlook, 2-wire smoke support,
keyswitch arming, 24 hour operation or forced answer.
PGM2 outputs are connected
the same way as PGM1
outputs.
PGM Output Options [01] - [15]
Both programmable outputs – PGM1 and PGM2 – on the
main board can be programmed by selecting one of the
output options listed below.
PGM output options [01] to [15] can be programmed for
both PGM1 and PGM2.
Main Board PGM Outputs................................. Section [06]
[01] Ground Start Pulse
The PGM Output will activate for two seconds to obtain a dial
tone on Ground Start telephone equipment before the panel
attempts to dial. Two 2-second pauses should be inserted at
the beginning of the phone number when using this option.
[02] Utility Output with any Access Code
The PGM output will activate for 5 seconds when the [
✱] [7]
[1] [Access Code] command is entered (see Section 3.0 –
“Keypad Commands”).
[03] Sensor Reset
This output will normally be active and switched
to ground.
This option is used to reset power for latching smoke
detectors. The output will deactivate for five seconds when
the [
✱] [7] [2] command is entered (see Section 3.4 “[✱] [7]
Output Functions”). The keypad buzzer will not sound for
the five second period.
Please refer to the Hook-Up diagram in this manual for
wiring instructions.
[04] Courtesy Pulse
Upon arming, the PGM output will activate for the duration
of the exit delay plus an additional two minutes. Upon entry,
the PGM output will activate for the duration of the entry
delay plus an additional two minutes.
[05] Keypad Buzzer Follower Mode
The PGM will activate when any of the following events
occur and will remain active for as long as the keypad
buzzer is active:
• Door Chime • Entry Delay
• Auto-Arm Prealert • Audible Exit Delay
• 24 Hour Supervisory Buzzer Zone
[06] System Armed Status
When the system is armed, the PGM output will switch to
ground at the beginning of the exit delay. The output goes
high (open) when the panel is disarmed.
[07] Latched System Event (Strobe Output)
The PGM output will switch to ground when any of the
system events (alarms) occur on the system. In the armed
state, the output will deactivate only when the system is
disarmed. If an alarm activates this output in the disarmed
state, the output will deactivate if the bell is silenced during
a bell time-out, or if the system is armed after the bell time-
out. This PGM output can be used to indicate that an alarm
has occurred before entering the premises.
This output will activate for all silent and audible alarms of
the following types:
Burglary .......Delay, Instant, Interior, Stay/Away and 24
Hour Burglary Zones
Fire ...............Fire Keys, Fire Zone and 2-wire Smoke Zone
(PGM Output)
Panic............ Panic Keys and Panic
Auxiliary ....... Auxiliary Keys, Auxiliary and Emergency
Zones
Supervisory..Supervisory, Freezer and Water Zones
Priority..........Heat, Sprinkler and 24 Hour Latching Zones
This output will activate for alarm conditions
only. Pre-alerts or delays will not activate the
output. This output should only be activated for
all audible alarms or medical conditions
[08] Failure to Communicate or Telephone Line
Monitoring Trouble
The PGM output switches to ground when either of the two
telephone line troubles are detected on the system (see
Section 3.4 – “[
✱] Commands; [✱] [2] Trouble Conditions”).
The output will deactivate when neither trouble is present.
[09] Entry Delay Follower
The PGM output switches to ground for the duration of the
Entry Delay.
[10] Exit Delay Follower
The PGM output switches to ground for the duration of the
Exit Delay.
If this feature is used in conjunction with courtesy
pulse, it will terminate at the end of the courtesy
pulse time, not at the end of the exit delay.
PGM Output Options
A P P E N D I X D
Comentarios a estos manuales