P R O G R A M D E S C R I P T I O N S
Periodic Test Transmission Reporting Code.. Section [46]
Test Transmission Time of Day ........................ Section [63]
Test Transmission Cycle.................................. Section [62]
LINKS 1000 Test Transmission Reporting Code Section [46]
System Test Reporting Code ........................... Section [46]
5.13 Fire, Auxiliary and Panic Keys – [F], [A], [P]
The emergency keys are available on all keypads. These
keys must be pressed and held for two seconds before they
will activate. This two second delay is designed to help
prevent accidental activation.
If the [F] Key option is enabled, when the Fire keys are
pressed and held for two seconds, the panel
will activate the alarm output, pulsing one second ON, one
second OFF. The alarm output will sound until a code is
entered or until the alarm output times out. Communication
of the signal to central station is immediate.
If the [A] Key is pressed and held for two seconds, the
panel will sound the keypad beeper
three times to verify activation. The panel will beep the
keypad ten times rapidly to verify communication to the
central station.
If the [P] Key is pressed and held for two seconds, the
panel will immediately communicate the
signal to central station. If [P] Key Audible Bell and
Buzzer option is enabled, the panel will beep the
keypad three times upon activation and activate the
alarm output until a code is entered or the alarm output
times out. Otherwise the alarm will be completely silent.
The Fire, Auxiliary, Panic keys will operate even if
Keypad Blanking is active (See Section 5.20 “Key-
pad Blanking”).
[F] Key Enable................................. Section [08], Option [3]
[P] Key Audible Bell and Buzzer.. Section [08], Option [4]
5.14 Arming /Disarming Options
If the Quick Arm option is enabled, the panel can be armed
without a user code by entering []
[0] or by pressing the
Stay or Away key on the LCD5500 or PC5506 keypads.
The Quick Exit option, if enabled, will allow someone to
leave an armed premises through a Delay type zone without
having to disarm and rearm the system.
If the Arm/Disarm Bell Squawk option is enabled, the panel
will squawk the alarm output once upon arming and twice
upon disarming. The Opening After Alarm Keypad
Ringback option will give you the ability to beep the keypad
10 times rapidly if the panel is disarmed after an alarm
occurred. The Opening After Alarm Bell Squawk
option
will give you the ability to squawk the bell output 10 times
rapidly if the panel is disarmed after an alarm occurred.
Closing Confirmation, if enabled, will cause the keypad to
beep 10 times rapidly after the closing Reporting Code has
been transmitted to central station.
If the Bypass Status Displayed While Armed is chosen,
the Bypass light will be ON while the system is armed to
indicate any bypassed zones.
Quick Arm Enable ......................... Section [10], Option [6]
Quick Exit Enable ........................... Section [09], Option [4]
Arm/Disarm Bell Squawk............... Section [10], Option [1]
Closing Confirmation..................... Section [61], Option [1]
Opening After Alarm Keypad Ringback . Section [61], Option [2]
Opening After Alarm Bell Ringback . Section [61], Option [3]
Bypass Status Displayed While Armed . Section [09], Option [5]
With Arm/Disarm Bell Squawk enabled, when a
[
][9] arming is performed, no squawk will sound.
5.15 Entry/Exit Delay Options
Upon arming, the panel will begin the exit delay. If the
Audible Exit Delay with Urgency option is enabled, the
keypad will beep at one second intervals until the exit delay
expires. The keypad will beep rapidly for the last 10 seconds
of exit delay to warn the user that the system is about to arm.
For commercial applications, the Bell Squawk on Exit
Delay option may be enabled. The panel will squawk the
alarm output once every second when the exit delay is
initiated and three times per second for the last 10 seconds
until the exit delay expires.
Upon entry, if a Delay type zone is violated, the panel will
begin the entry delay. The keypad will emit a steady tone.
The keypad will pulse the keypad sounder during the last 10
seconds to warn the user the system is about to go into
alarm. If there was an alarm during the armed period, the
keypad will pulse for the entire entry delay to warn the user
of the previous alarm.
For commercial applications Bell Squawk on Entry Delay
may be enabled. The panel will squawk the alarm output
once every second until the entry delay expires or the
system is disarmed.
Since two Delay zones – and therefore two different
Entry Delays – are programmable, when the panel is
armed, the Entry Delay will begin when the first
delay zone violated.
If the Bell Squawk During Auto Arm option is enabled, the
bell will squawk when the system is auto-armed in order to
notify anyone on the premises that the system is being
armed.
If the Exit Delay Termination option is enabled, the panel
will monitor the Delay zones during exit delay. During the
exit delay, if a Delay type zone is violated and then secured,
the exit delay will be terminated and the panel will be armed
immediately.
Entry Delay 1 and 2 (System Times) ............... Section [02]
Exit Delay (System Times)................................ Section [02]
Bell Squawk Options......................................... Section [10]
Audible Exit Delay .......................... Section [10], Option [5]
Exit Delay Termination .................. Section [11], Option [4]
5.16 Swinger Shutdown
The Swinger Shutdown feature is designed to prevent a
runaway communicator from tying up the central station.
After the panel has communicated the programmed number
of transmissions for an event, it will no longer report that
event until the Swinger Shutdown is reset.